Application area
The KNXnet/IP-Interface is used to connect a PC to the KNX/EIB network. The connection is made through LAN (IP).
The IP address can be obtained by a DHCP server or by manual configuration (ETS).
An additional power supply is required, ranging from 10 to 30 V DC.
This device works according to the KNXnet/IP specification using the core, the device management and the tunneling part.
Technical data
Electrical safety
Protection (EN 60529): IP 20
Safety extra low voltage SELV DC 24 V
EMC requirements
Complies with EN 61000-6-2, EN 61000-6-3 and EN 50090-2-2
Certification
EIB/KNX
CE norm
Complies with the EMC regulations (residential and functional buildings) and low voltage direc¬tive
Physical specifications
DIN Rail mounted device
Dimensions : 90 x 36 x 64 mm (H x W x D)
Weight: approx. 100 g
Indicators
Learning-LED (red) when in learning mode
Signal-LED (green) for Operating mode display
Signal-LED (yellow) for Network connection indicator & KNX telegram traffic indicator
Ethernet
10/100BaseT (10 or 100 Mbit/s)
Supported internet protocols ARP, ICMP, IGMP, UDP/IP and DHCP
Power supply
External supply 10-35 VDC
Power consumption: 1.9W at 10V
Connectors
EIB/KNX connection terminal
LAN RJ-45 socket for 10/100BaseT connection
Connector for power supply